Section 3: Installing the Instrument
05/11 26 51209 Revision 2
3.2.12 DeviceNet Interface (PR 5220/04 only)
It is a complete DeviceNet adapter (SLAVE) with CAN controller and transfer rates of up to 500
kbit/s.
Connection: 5-contact screw terminal block (plug-
in)
Transfer rate: 125, 250 and 500 kbit/s
Topology: Parallel bus
Protocol: DeviceNet master/slave
Polling method (polled I/O)
CRC error detection
to IEC 62026 (EN50325)
Max. 64 station nodes
Max. data width 512 bytes input &
output
Transport: EIA RS-485
Configuration: EDS file
MAC-ID (1…62)
Certificates/
conformity:
Compatible with DeviceNet
specification
Vol 1: 2.0, Vol 2: 2.0
ODVA certificate in accordance with
conformity test software version A-12
Suitable for industrial applications to
CE, UL and cUL
Cable: DeviceNet, color: petrol-green
2x2 shielded twisted pair
Cable impedance: 150 ohms
Bus termination: 120 ohms at the cable ends
Electrical isolation:
Yes, optocoupler and DC/DC
converter
Connecting diagram for a master with three slaves